Outdoor Air Sensor – Quad

TS1003

Description

Utility box contains four sensors for wiring to multiple controllers. Outdoor air sensors are enclosed in a sealed standard aluminum box and includes conduit junction. Sensors can be converted for duct-mounting applications by changing the position of the PVC probe.

Single-point sensor accuracy:

+/–0.1% @ 32°F (0°C)

Averaging sensor accuracy:

+/–1°F @ 70°F (21.11°C)

Temperature coefficient: 

0.00385 Ω/Ω/°C

Reference resistance: 

1000Ω @ 32°F (0°C)

Compliance:

DIN IEC 751

Response time (90%):

  • Air @1m/s: 25 seconds
  • Air @3m/s: 17 seconds

Operating temperature:

–50 to 375°F (–45.6 to 190.6°C)

Maximum current:

5 mA; recommended: 1 mA