SZ1064

Modulating Fan Coil Thermostats

Description

The SZ1060 Series is designed for fan coil
applications that require digital (SZ1061 and
SZ1062) or modulating (SZ1063 and SZ1064)
heating and/or cooling.

Features:

• Stand-alone or network operation
• P+I control option (SZ1061 and SZ1062 only)
• No battery backup required
• Minimum on/off times for HVAC equipment
protection
• 32-character LCD display
• Six status LEDs
• Remote room sensing capability
• User setpoint adjustment limits
• Three speed fan
• System and fan switching with access lockouts
• External input for setback or aquastat changeover
• Access to programming may be locked out or
limited with the use of an access code
• Fahrenheit or Celsius temperature display
• Control for two or four pipe systems
Additional features on SZ1062 and SZ1064:
• 7-day programmable time clock
• Optional pipe sensor input for changeover
• Adjustable delay on start-up and power-up for
soft starts
• Smart recovery
• Local and remote override capability
• External time clock and override options
• Auxiliary output for heat, cool or time clock

Call to order:

1-800-288-9383

Specs & Docs

Specifications:

General
Accuracy: +/- 1ºF at 75ºF
Display resolution: +/-1°F (0.6°C)
Display: 32-character LCD
Programming: Front panel keypad or EIA RS485 interface
Communications: RS485, half duplex
Memory backup: Non-volatile EEPROM, no battery required
Environmental
Operating temperature: 32 to 131°F (0 to 55°C)
Operating humidity: 0 to 100% RH, non-condensing
Storage temperature: 14 to 140°F (-10 to 60°C)

Electrical
Supply voltage: 24 VAC +/- 20%
SZ1061 and SZ1063
Inputs: Built-in and remote platinum RTDs, three digital (dry contact)
Range: Room Temp: 40 to 90°F (built-in or remote)
SZ1061 Outputs: 5 digital (SPST dry contact, 24VAC @ 2A max.)
SZ1063 Ouputs: 3 digital (SPST dry contact 24VAC @ 2A max.) and two 4-20mA DC analog max. Load Resistance (analog outputs): 600 Ω
SZ1062 and SZ1064
Inputs: Built-in and remote platinum RTD’S momentary override and three digital (dry contact)
Range: Room Temp: 40 to 90°F (built-in or remote)
Pipe Temp: 0 to 150°F(remote)
SZ1062 Outputs: 6 digital (SPST dry contact, 24VAC @ 2A max.)
SZ1064 Ouputs: 4 digital (SPST dry contact 24VAC @ 2A max.) and two 4-20mA DC analog max. Load Resistance (analog outputs) 600 Ω
Common mode rejection: 100db @ 60 Hz
Power Consumption: 8 VA max.
Specifications subject to change without notice